This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
operations:documentation.errors [2017/08/13 22:15] Tiege McCarthy |
operations:documentation.errors [2017/09/27 06:29] (current) Jamie McCallum [Antenna stuck | Warning: error st -27 computer acu time difference exceeded 0.25 seconds, see value above.] |
||
---|---|---|---|
Line 42: | Line 42: | ||
==== Antenna stuck | Warning: error st -27 computer acu time difference exceeded 0.25 seconds, see value above. ==== | ==== Antenna stuck | Warning: error st -27 computer acu time difference exceeded 0.25 seconds, see value above. ==== | ||
- | Normally this error can be ignored, but there was an additional error with this - WARNING: error st -10 rampepochtime not -1 when preparing to load, check antenna is in "operate". Error presented as drive status not ready, with drives green in HMI. HMI was unresponsive - could not turn drives off. Antenna=operate and Antenna=open both return Antenna OK, but don't work. The clock on the right of HMI interface on cnsshb (CURRENT TIME UT1) was not updating. | + | Normally this error can be ignored, but there was an additional error: |
+ | |||
+ | <code> | ||
+ | WARNING: error st -10 rampepochtime not -1 when preparing to load, check antenna is in "operate". | ||
+ | </code> | ||
+ | |||
+ | Error presented as drive status not ready, with drives green in HMI. HMI was unresponsive - could not turn drives off. Antenna=operate and Antenna=open both return Antenna OK, but don't work. The clock on the right of HMI interface on cnsshb (CURRENT TIME UT1) was not updating. | ||
Solution to issue is using HMI and selecting the reboot central button under resets. This reset the clock connection to the antenna, allowing the drives to communicate again. | Solution to issue is using HMI and selecting the reboot central button under resets. This reset the clock connection to the antenna, allowing the drives to communicate again. |