blog:katherine_temperature_humidity_sensors [2014/07/24 10:40] Jamie McCallum |
blog:katherine_temperature_humidity_sensors [2014/07/29 01:43] (current) Jamie McCallum |
||
|---|---|---|---|
| Line 14: | Line 14: | ||
| TrueTemp=MonicaTemp | TrueTemp=MonicaTemp | ||
| + | |||
| + | The temperature and humidity sensors in the Katherine pedestal and hub have been recalibrated using the data from the loggers (29/7/14 ~0140 UT). Data from Monica recorded before this time can be rescaled using the formulae below: | ||
| + | |||
| + | **Pedestal:** | ||
| + | |||
| + | TrueRH = MonicaRH*0.95 + 23 | ||
| + | |||
| + | TrueTemp=MonicaTemp*0.92 + 0.32 | ||
| + | |||
| + | **Hub:** | ||
| + | |||
| + | TrueRH = MonicaRH * 0.83 +27 | ||
| + | |||
| + | TrueTemp=MonicaTemp *0.93 +0.77 | ||
| + | |||
| + | **Feed** | ||
| + | |||
| + | Feed temp & RH sensors still not working. | ||