This shows you the differences between two versions of the page.
Next revision | Previous revision | ||
blog:katherine_temperature_humidity_sensors [2014/07/24 10:37] Jamie McCallum |
blog:katherine_temperature_humidity_sensors [2014/07/29 01:43] (current) Jamie McCallum |
||
---|---|---|---|
Line 3: | Line 3: | ||
The temperature and humidity sensors in the Katherine control and maser rooms have been recalibrated using the data from the loggers (24/7/14, ~1030 UT). Data from Monica recorded before this time can be rescaled using the formulae below: | The temperature and humidity sensors in the Katherine control and maser rooms have been recalibrated using the data from the loggers (24/7/14, ~1030 UT). Data from Monica recorded before this time can be rescaled using the formulae below: | ||
- | Control Room: | + | **Control Room:** |
TrueRH = MonicaRH*1.2 + 4,7 | TrueRH = MonicaRH*1.2 + 4,7 | ||
+ | |||
TrueTemp=MonicaTemp*0.9 + 0.66 | TrueTemp=MonicaTemp*0.9 + 0.66 | ||
- | Maser Room: | + | **Maser Room:** |
TrueRH = MonicaRH*0.83+32 | TrueRH = MonicaRH*0.83+32 | ||
+ | |||
TrueTemp=MonicaTemp | TrueTemp=MonicaTemp | ||
+ | |||
+ | The temperature and humidity sensors in the Katherine pedestal and hub have been recalibrated using the data from the loggers (29/7/14 ~0140 UT). Data from Monica recorded before this time can be rescaled using the formulae below: | ||
+ | |||
+ | **Pedestal:** | ||
+ | |||
+ | TrueRH = MonicaRH*0.95 + 23 | ||
+ | |||
+ | TrueTemp=MonicaTemp*0.92 + 0.32 | ||
+ | |||
+ | **Hub:** | ||
+ | |||
+ | TrueRH = MonicaRH * 0.83 +27 | ||
+ | |||
+ | TrueTemp=MonicaTemp *0.93 +0.77 | ||
+ | |||
+ | **Feed** | ||
+ | |||
+ | Feed temp & RH sensors still not working. | ||
{{tag>}} | {{tag>}} | ||
+ | |||
~~DISCUSSION~~ | ~~DISCUSSION~~ |