This shows you the differences between two versions of the page.
| Both sides previous revision Previous revision Next revision | Previous revision | ||
|
deformation:testsetup1 [2012/08/29 04:48] Jim Lovell [PC Software] |
deformation:testsetup1 [2012/11/29 05:19] (current) Jim Lovell [PC Software] |
||
|---|---|---|---|
| Line 28: | Line 28: | ||
| * Came up on COM3, 9600 baud, 8 bit, parity none, stop bits 1, flow control none. | * Came up on COM3, 9600 baud, 8 bit, parity none, stop bits 1, flow control none. | ||
| * Connected power to logger via DC power-pack. No luck. Direct connection to battery works | * Connected power to logger via DC power-pack. No luck. Direct connection to battery works | ||
| - | * MAC address for Array 1 00d02c04b057 | + | * MAC address for Array 1 00d02c04b057, Array 2 00d02c04b051 and temporary IP addresses are 131.217.62.92 and .93 respectively and called AUScope-Array1.phys... and AUScope-Array2.phys... |
| + | * In Device Config Utility, | ||
| + | * Connection over serial with ethernet plugged in, shown DHCP working and TCP port set to 6785 | ||
| + | * In Datalogger tab, Station name is Array1, PakBus Address 1, security code 0 | ||
| + | * edited .cipasswd file (New Services Tab) to give usual observer password for admin, FTP password for anonymous is the same | ||
| + | * In logger Control, hit Set clock (synchs with PC clock, so that needs to be on an NTP server) | ||
| + | * In data monitor, can see logged data (after plugging in sensors), other stats like batther level etc. | ||
| + | * Finished, so disconnect. | ||
| + | * Now in EZSetup Wizzard | ||
| + | * IP address set to 131.217.62.92:6785, pakbus 1, security code 0 | ||
| + | * Comm test worked! | ||
| + | * Configured Array2 as above, just different name and I address, PakBus Address 1 (tried 2 but failed the comms test). | ||