The temperature and humidity sensors in the Katherine control and maser rooms have been recalibrated using the data from the loggers (24/7/14, ~1030 UT). Data from Monica recorded before this time can be rescaled using the formulae below:
Control Room:
TrueRH = MonicaRH*1.2 + 4,7
TrueTemp=MonicaTemp*0.9 + 0.66
Maser Room:
TrueRH = MonicaRH*0.83+32
TrueTemp=MonicaTemp
The temperature and humidity sensors in the Katherine pedestal and hub have been recalibrated using the data from the loggers (29/7/14 ~0140 UT). Data from Monica recorded before this time can be rescaled using the formulae below:
Pedestal:
TrueRH = MonicaRH*0.95 + 23
TrueTemp=MonicaTemp*0.92 + 0.32
Hub:
TrueRH = MonicaRH * 0.83 +27
TrueTemp=MonicaTemp *0.93 +0.77
Feed
Feed temp & RH sensors still not working.