This is an old revision of the document!
The temperature and humidity sensors in the Katherine control and maser rooms have been recalibrated using the data from the loggers (24/7/14, ~1030 UT). Data from Monica recorded before this time can be rescaled using the formulae below:
Control Room:
TrueRH = MonicaRH*1.2 + 4,7
TrueTemp=MonicaTemp*0.9 + 0.66
Maser Room:
TrueRH = MonicaRH*0.83+32
TrueTemp=MonicaTemp
The temperature and humidity sensors in the Katherine pedestal and hub have been recalibrated using the data from the loggers (date and time). Data from Monica recorded before this time can be rescaled using the formulae below:
Pedestal:
TrueRH = MonicaRH*0.95 + 23
TrueTemp=MonicaTemp*0.92 + 0.32
Hub:
TrueRH = MonicaRH
TrueTemp=MonicaTemp
Feed
Feed temp & RH sensors newly installed.